LVB series HV outdoor AC oil-insulated inverted current transformer meets all IEC and GB metering and protection classes (other standards on request). This current transformer has highly refined and processed oil/paper insulation system, high level of insulation, and good character of outside insulation. Also, it is light weight and requires very little oil.
LVB series current transformer has temporary protective winding, meets with big capacity of power system, and reclosing operation. Oil tank is made of corrosion-resistant materials, no maintenance outside.
Part Ⅰ: Operating Characteristics
Location: indoor or outdoor
Ambient temperature: -40℃ - +45℃ (Freezing field can meet -45℃)
Wind load: not exceed 35 m/s
Altitude: not exceed 3000m
Icing thickness: not exceed 10mm
Seismic strength: 8
Pollution level: lII or IV
Note: If the product using conditions beyond the above provisions, please contact us and we can solve as quick as possible.
Part Ⅱ: Demonstration of The Type
For example: type LVB-110W2 means that this CT gives extra the protection level winding for the inverted structure, may use in the Rated system voltage 100kV and can be used for pollution level Ⅲ area.
Part Ⅲ: Product Sectional View and Electrical Diagrams
Part Ⅳ: Products Design Features and Advantages
1. Highly refined and processed oil/paper insulation system and advanced technology, the electric strength of CT is improved obviously, guarantee the product operation reliability effectively.
2. The drive pipe which the company used has actually long creepage distance, the results of creepage distance/dry arcing di stance is rational. It improves the margin of the outer insulation resistance effectively, enhance pollution resistance.
3. Reasonable structure of the media and design, advanced technology which can make the dielectric loss (tan 6 ) reduced to below 0.5%, and steady in the long run.
4. Hight mechanical strength drive pipe and optimized structure design, it improves product mechanical strength.
5. Good seals and optimization structure, second terminal board using lead with epoxy resin conductive stem overall vacuum pouring parts, which can ensure do not produce oil leakage phenomenon.
6. Excellent seismic performance as a consequence of optimized designs of flanges, porcelain and their interconnection.
7. Lower dissipation, and steady in the long run.
8. Short primary conducting, Good Dynamic and Thermal Stability.
Part Ⅴ: Main Technical Data
Transformer type | LVBT-500W2 | LVBT-330W2 | LVBT-220W3 | LVB-220W3 | LVB-110W3 | LVB-66W3 | |
Highest system voltage | kV | 550 | 363 | 252 | 252 | 126 | 72.5 |
Rated freguency | Hz | 50 | 50 | 50 | 50 | 50 | 50 |
Power freguency withstand voltage | kV | 680 | 510 | 460 | 460 | 230 | 160 |
BIL, 1.2/50 p s foil ware | kV | 1175 | 950 | / | / | / | / |
Chopped test | kV | 1550 | 1175 | 1050 | 1050 | 550 | 350 |
Flashover distance | mm | 3930 | 2675 | 2195 | 2200 | 1220 | 1200 |
Creepage distance | mm | ≥13750 | ≥11253 | ≥7812 | ≥7812 | ≥3906 | ≥2248 |
Rated primary current | A | 4000 | 4000 | 4000 | 4000 | 3000 | 3000 |
Rated secondary current | A | 5;1 | 5;1 | 5;1 | 5;1 | 5;1 | 5;1 |
Accuracy class (Upon request) | 0.1; 0.2S; 0.5; 5P; 10P; TPY | 0.1; 0.2S; 0.5; 5P; 10P; TPY | 0.1; 0.2S; 0.5; 5P; 10P; TPY | 0.2S; 0.5; 5P; 10P | 0.2S; 0.5; 5P; 10P | 0.2S; 0.5; 5P; 10P | |
Rated output | VA | 10-50 | 10-50 | 10-50 | 10-50 | 10-50 | 10-50 |
Instrument secutity fector | FS | 5; 10 | 5; 10 | 5; 10 | 5; 10 | 5; 10 | 5; 10 |
Rated accuracy limit fector | 30 | 30 | 30 | 30 | 30 | 30 | |
Rated Short-time current/3s (max) lth | kA | 63 | 63 | 63 | 63 | 50 | 50 |
Rated dynamic current (max) ldyn | kA | 160 | 160 | 160 | 160 | 125 | 125 |
Dimensions | mm | 1000 X 1200 X 6200 | 745 X 1127 X 4265 | 745 X 1060 X 3745 | 604 X 980 X 3650 | 535 (604) X 780 (930) X 2230 (2370) | 535 (604) X 780 (930) X 2230 (2370) |
Mounting size | mm | 650 X 650 | 600 X 600 | 600 X 600 | 600 X 600 | 450 X 450 | 450 X 450 |
Net weight | Kg | 2250 | 1000 | 800 | 500 | 480 | 480 |
Gross weight | Kg | 3100 | 1350 | 1070 | 790 | 550 | 550 |
Part Ⅵ: Application
Part Ⅶ: Note for Ordering
1. The type and name of the product
2. The rated voltage, rated current ratio, rated output and accuracy class
3. Pollution level
4. Altitude
5. Providing special products for your demand
Part Ⅷ: Service Guarantee
1. Quickly and professional response;
2. Excellent quality with reasonable price;
3. Sufficient support for our tendering representatives;
4. OEM service available based on official & legal authorization;
5. Strict quality control system;
6. Faster lead time than our competitors;
7. 12 months quality guarantee after delivery.
Part Ⅸ: FAQ
Q1: What is your delivery time?
Depend on the type of transformer.
Q2: What is your payment term?
30% advance by T/T , 70% before delivery by T/T or L/C or we can discuss about it.
Q3: What kind of standard you follow?
IEC, ANSI, CSA, GB, etc
Q4: What kind of supporting documentation you can provide normally?
Quotation, outline drawing, manufacturing plan, quality control plan testing plan, financial report, type test report (KEMA, CESI), reference list, etc.
Q5: What is your normal warranty period?
12 months after transformer operation.
Hot Tags: lvb series hv outdoor ac oil-insulated inverted current transformer, China, suppliers, manufacturers, factory, price, made in China