LVB Series HV Outdoor AC Oil-Insulated Inverted Current Transformer

​LVB series HV outdoor AC oil-insulated inverted current transformer meets all IEC and GB metering and protection classes (other standards on request). This current transformer has highly refined and processed oil/paper insulation system, high level of insulation, and good character of outside insulation. Also, it is light weight and requires very little oil.
Send Inquiry

Product Introduction

LVB series HV outdoor AC oil-insulated inverted current transformer meets all IEC and GB metering and protection classes (other standards on request). This current transformer has highly refined and processed oil/paper insulation system, high level of insulation, and good character of outside insulation. Also, it is light weight and requires very little oil.


LVB series current transformer has temporary protective winding, meets with big capacity of power system, and reclosing operation. Oil tank is made of corrosion-resistant materials, no maintenance outside.


Part Ⅰ: Operating Characteristics

Location: indoor or outdoor

Ambient temperature: -40℃ - +45℃ (Freezing field can meet -45℃)

Wind load: not exceed 35 m/s

Altitude: not exceed 3000m

Icing thickness: not exceed 10mm

Seismic strength: 8

Pollution level: lII or IV

Note: If the product using conditions beyond the above provisions, please contact us and we can solve as quick as possible.


Part Ⅱ: Demonstration of The Type

1


For example: type LVB-110W2 means that this CT gives extra the protection level winding for the inverted structure, may use in the Rated system voltage 100kV and can be used for pollution level Ⅲ area.


Part Ⅲ: Product Sectional View and Electrical Diagrams

2


Part Ⅳ: Products Design Features and Advantages

1. Highly refined and processed oil/paper insulation system and advanced technology, the electric strength of CT is improved obviously, guarantee the product operation reliability effectively.

2. The drive pipe which the company used has actually long creepage distance, the results of creepage distance/dry arcing di stance is rational. It improves the margin of the outer insulation resistance effectively, enhance pollution resistance.

3. Reasonable structure of the media and design, advanced technology which can make the dielectric loss (tan 6 ) reduced to below 0.5%, and steady in the long run.

4. Hight mechanical strength drive pipe and optimized structure design, it improves product mechanical strength.

5. Good seals and optimization structure, second terminal board using lead with epoxy resin conductive stem overall vacuum pouring parts, which can ensure do not produce oil leakage phenomenon.

6. Excellent seismic performance as a consequence of optimized designs of flanges, porcelain and their interconnection.

7. Lower dissipation, and steady in the long run.

8. Short primary conducting, Good Dynamic and Thermal Stability.


Part Ⅴ: Main Technical Data

Transformer type

LVBT-500W2

LVBT-330W2

LVBT-220W3

LVB-220W3

LVB-110W3

LVB-66W3

Highest system voltage

kV

550

363

252

252

126

72.5

Rated freguency

Hz

50

50

50

50

50

50

Power freguency withstand voltage

kV

680

510

460

460

230

160

BIL, 1.2/50 p s foil ware

kV

1175

950

/

/

/

/

Chopped test

kV

1550

1175

1050

1050

550

350

Flashover distance

mm

3930

2675

2195

2200

1220

1200

Creepage distance

mm

≥13750

≥11253

≥7812

≥7812

≥3906

≥2248

Rated primary current

A

4000

4000

4000

4000

3000

3000

Rated secondary current

A

5;1

5;1

5;1

5;1

5;1

5;1

Accuracy class (Upon request)


0.1; 0.2S; 0.5; 5P; 10P; TPY

0.1; 0.2S; 0.5; 5P; 10P; TPY

0.1; 0.2S; 0.5; 5P; 10P; TPY

0.2S; 0.5; 5P; 10P

0.2S; 0.5; 5P; 10P

0.2S; 0.5; 5P; 10P

Rated output

VA

10-50

10-50

10-50

10-50

10-50

10-50

Instrument secutity fector

FS

5; 10

5; 10

5; 10

5; 10

5; 10

5; 10

Rated accuracy limit fector


30

30

30

30

30

30

Rated Short-time current/3s (max) lth

kA

63

63

63

63

50

50

Rated dynamic current (max) ldyn

kA

160

160

160

160

125

125

Dimensions

mm

1000 X 1200 X 6200

745 X 1127 X 4265

745 X 1060 X 3745

604 X 980 X 3650

535 (604) X 780 (930) X 2230 (2370)

535 (604) X 780 (930) X 2230 (2370)

Mounting size

mm

650 X 650

600 X 600

600 X 600

600 X 600

450 X 450

450 X 450

Net weight

Kg

2250

1000

800

500

480

480

Gross weight

Kg

3100

1350

1070

790

550

550


Part Ⅵ: Application

3


Part Ⅶ: Note for Ordering

1. The type and name of the product

2. The rated voltage, rated current ratio, rated output and accuracy class

3. Pollution level

4. Altitude

5. Providing special products for your demand


Part Ⅷ: Service Guarantee

1. Quickly and professional response;

2. Excellent quality with reasonable price;

3. Sufficient support for our tendering representatives;

4. OEM service available based on official & legal authorization;

5. Strict quality control system;

6. Faster lead time than our competitors;

7. 12 months quality guarantee after delivery.


Part Ⅸ: FAQ

Q1: What is your delivery time?

Depend on the type of transformer.


Q2: What is your payment term?

30% advance by T/T , 70% before delivery by T/T or L/C or we can discuss about it.


Q3: What kind of standard you follow?

IEC, ANSI, CSA, GB, etc


Q4: What kind of supporting documentation you can provide normally?

Quotation, outline drawing, manufacturing plan, quality control plan testing plan, financial report, type test report (KEMA, CESI), reference list, etc.


Q5: What is your normal warranty period?

12 months after transformer operation.


Hot Tags: lvb series hv outdoor ac oil-insulated inverted current transformer, China, suppliers, manufacturers, factory, price, made in China

Send Inquiry

(0/10)

clearall