MV XLPE Insulated Power Cable 3.6/6kV~26/35kV YJV YJLV Cable

​MV XLPE insulated power cable, either chemical method or physical method had been employed to transform the molecular structure of PE from chain into three-dimensional network, i.e. thermoplastic PE had been transformed into thermosetting XLPE. After cross-linking, the heat-mechanical properties of the cable have been greatly improved while its excellent electrical are still maintained.
Send Inquiry

Product Introduction

MV XLPE insulated power cable, either chemical method or physical method had been employed to transform the molecular structure of PE from chain into three-dimensional network, i.e. thermoplastic PE had been transformed into thermosetting XLPE. After cross-linking, the heat-mechanical properties of the cable have been greatly improved while its excellent electrical are still maintained.

The nominal conductor operating temperature of XLPE insulated power cable is 90°C which is higher than that of paper, PVC or PE insulated power cable. The cable has the advantages of simplicity in construction, lightness in weight, besides its excellent electrical, heat-mechanical and anti-chemical corrosion properties. It can also be laid with no limitation of level difference along the route.


Part Ⅰ: Operating Characteristics

1. Type: YJV (Copper Conductor XLPE insulated PVC sheathed power cable)

YJLV (Aluminum Conductor XLPE insulated PVC sheathed power cable)

YJY (Copper Conductor XLPE insulated PE sheathed power cable)

YJLV (Aluminum Conductor XLPE insulated PE sheathed power cable)

YJV62 (Copper conductor XLPE insulated non-magnetic metal tape armoured PVC sheathed Power cable)

YJLV62 (Aluminium conductor XLPE insulated non-magnetic metal tape armoured PVC sheathed Power cable)

YJV63 (Copper conductor XLPE insulated non-magnetic metal tape armoured PE sheathed Power cable)

YJLV63 (Aluminium conductor XLPE insulated non-magnetic metal tape armoured PEsheathed Power cable)

YJV22 (Copper Conductor XLPE insulated steel tape armored PVC sheathed power cable)

YJLV22 (Aluminum Conductor XLPE insulated steel tape armored PVC sheathed power cable)

YJV23 (Copper conductor XLPE insulated steel tape armoured PE sheathed power cable)

YJLV23 (Aluminium conductor XLPE insulated steel tape armoured PE sheathed power cable)

YJL72 (Copper conductor XLPE insulated non-magnetic metal wire armoured PVC sheathed power cable)

YJLV72 (Aluminum conductor XLPE insulated non-magnetic metal wire armoured PVC sheathed power cable)

YJV73 (Copper conductor XLPE insulated non-magnetic metal wire armoured PE sheathed power cable)

YJLV73 (Aluminum conductor XLPE insulated non-magnetic metal wire armoured PE sheathed power cable)

YJV32 (Copper Conductor XLPE insulated fine steel wire armored PVC sheathed power cable)

YJLV32 (Aluminum Conductor XLPE insulated fine steel wire armored PVC sheathed power cable)

YJV33 (Copper conductor XLPE insulated fine steel wire armoured PE sheathed power cable)

YJLV33 (Aluminium conductor XLPE insulated fine steel wire armoured PE sheathed power cable)

YJV42 (Copper core XLPE insulated thick steel wire armoured PVC sheathed power cable)

YJLV42 (Aluminum core XLPE insulated thick steel wire armoured PVC sheathed power cable)

YJV43 (Copper core XLPE insulated steel thick wire armoured PE sheathed power cable)

YJLV43 (Aluminium core XLPE insulated thick steel wire armoured PE sheathed power cable)

2. Rated power-frequency voltage Uo/U: 3.6/6kV ~26/35kV

3. Conductor: Oxygen-free Copper/Oxygen-free Aluminum

4. Insulation: XLPE

5. Sheathing: PVC/PE

6. Armored: Steel tape Armored (YJV22, YJLV22, YJV23, YJLV23)

Fine steel wire Armored (YJV32, YJLV32, YJV33, YJLV33)

Non-magnetic metal tape armored (YJV62,YJLV62, YJV63, YJLV63)

Non-magnetic metal wire armored (YJV72, YJLV72, YJV73, YJLV73)

Thick steel wire armored (YLV42, YJLV42, YJV43, YJLV43)

7. Max. admissible operating temperature of conductor: 90℃ (XLPE insulation)

8. Max. Short-circurt temperature of conductor shall not exceeding 250℃ (Max. sustaining period not exceeding 5S)

9. The installation temperature should be not below 0℃.

10. The bending radius of three-cores unarmored cable should not less than 15 times, and the bending radius of three-cores armored cable should not less than 12 times.

The bending radius of single core unarmored cable should not less than 20 times and the bending radius of single core armored cable should not less than 15 times.


Part Ⅱ: Range of Production

Structure
Type

Cores

Rated Voltage (kV)

3.6/6

6/6
6/10

8.7/10
8.7/15

12/15
12/20

18/20
18/30

21/35

26/35

Unarmored

1

Type

YJV YJLV YJY YJLY

YJSV YJLSV
YJSY YJSY

Nominal cross sectional of areas (mm2)

25~630

25~800

25~800

35~800

50~800

50~800

50~800

3

Type

YJV YJLV YJY YJLY

Nominal cross sectional of areas (mm2)

25~630

25~630

25~630

35~630

50~500

50~500

50~500

Non-magnetic
Metal tape armored

1

Type

YJV62 YJLV62 YJV63 YJLV63

YJSV62 YJLSV62
YJSY63 YJSY63

Nominal cross sectional of areas (mm2)

25~630

25~800

25~800

35~800

50~800

50~800

50~800

Steel tape armored

3

Type

YJV22 YJLV22 YJV23 YJLV23

Nominal cross sectional of areas (mm2)

25~630

25~630

25~630

35~630

50~500

50~500

50~500

Non-magnetic metal wire armored

1

Type

YJV72 YJLV72 YJV73 YJLV73

YJSV72 YJLSV72
YJSV73 YJLSV73

Nominal cross sectional of areas (mm2)

25~630

25~800

25~800

35~800

50~800

50~800

50~800

Steel wire
armored

3

Type

YJV32 YJLV32 YJV33 YJLV33

Nominal cross sectional of areas (mm2)

25~630

25~630

25~500

35~500

50~400

50~300

50~185

Thick Steel
Wire armored

1/3

Type

YJV42 YJLV42 YJV43 YJLV43

Nominal cross sectional of areas (mm2)

25~630

25~630

25~500

35~500

50~400

50~300

50~185


Part Ⅲ: Construction

1


The type conductor is compact and the circular conductor is made up of round conductor wires. The comparison diagrams of the two conductor structures are shown above. Both meet the national standard.


Compared with circular conductor, type conductor:

1) More compact and higher compression coefficient;

2) Better waterproof performance;

3) The field intensity distribution on the conductor's surface is more uniform;

4) Can avoid the conductor shield stuck between the conductor stranded;

5) For the same specification, the diameter of the type conductor is smaller, so that the cable is more affordable.


Part Ⅳ: Construction and Main Technical Data

3.6/6kV 1 Core XLPE insulated PVC Sheathed Power Cable
Nominal cross sectional areasDiameter of conductorInsulation thicknessOuter Sheath ThicknessApprox, overall DiameterCable approx. weight
mmkg/km
YJV YJLVYJVYJLV
mm²±0.1mmmmmmZA/ZBZC/Non-flame retardantZAZBZCNon-flame retardantZAZBZCNon-flame retardant
255.92.51.821±0.819±0.8580556506496432408358348
356.92.51.822±0.820±0.8691665613603485459407396
508.22.51.823±0.821±0.8833806750739553526470459
709.72.51.824±0.822±0.810381010951939632603544532
9511.42.51.826±0.824±0.81316128612221209746716652639
12012.92.51.827±0.825±0.81572154014731459852820752738
15014.22.51.829±0.827±0.81847181317421727964930858843
18516.02.51.931±0.829±0.82229218921132097112010811004988
24018.32.61.934±1.331±0.828012758267526571345130212191201
30020.52.82.036±1.334±1.334233375328432641600155214611441
40023.33.02.240±1.338±1.343204266416441422006195118471824
50026.33.22.344±1.342±1.354425377526452392438237322592234
63030.03.22.448±1.346±1.368436770664566182952287927552727
24017.62.61.933±1.330±0.82774273326512634



30019.62.82.035±1.334±1.33397335032613242




6/6kV.6/10kV 1 Core XLPE insulated PVC Sheathed Power Cable
Nominal cross sectional areasDiameter of conductorInsulation thicknessOuter Sheath ThicknessApprox, overall DiameterCable approx. weight
mmkg/km
YJV YJLVYJVYJLV
mm²±0.1mmmmmmZA/ZBZC/Non-flame retardantZAZBZCNon-flame retardantZAZBZCNon-flame retardant
255.93.41.822±0.820±0.8639613559548491465411400
356.93.41.823±0.821±0.8752725668657547519462451
508.23.41.825±0.823±0.8898869809796618589529516
709.73.41.826±0.824±0.8110510751012999699669605592
9511.43.41.827±0.825±0.81387135512871273818785717703
12012.93.41.829±0.827±0.81647161315411526927893821806
15014.23.41.930±0.828±0.8193818991823180710571017940924
18516.03.41.933±1.330±0.823122270218921721203116110801063
24018.33.42.035±1.333±1.328942848276027411438139213041285
30020.53.42.138±1.336±1.335013452335733371677162915341513
40023.33.42.241±1.339±1.343614306420241802048199218861863
50026.33.42.344±1.342±1.354595394528052552455239022752250
63030.03.42.448±1.346±1.368616788666366352970289727722744
80033.83.42.552±1.350±1.385748491835483243596351433763345
24017.63.42.034±1.333±1.32866282027342716



30019.63.42.137±1.335±1.33472342533323312




8.7/10kV.8.7/15kV 1 Core XLPE insulated PVC Sheathed Power Cable
Nominal cross sectional areasDiameter of conductorInsulation thicknessOuter Sheath ThicknessApprox, overall DiameterCable approx. weight
mmkg/km
YJV YJLVYJVYJLV
mm²±0.1mmmmmmZA/ZBZC/Non-flame retardantZAZBZCNon-flame retardantZAZBZCNon-flame retardant
255.94.51.824±0.822±0.8718689630618570542482470
356.94.51.825±0.823±0.8834804742729628599536524
508.24.51.827±0.825±0.8983952886873704672607593
709.74.51.828±0.826±0.81194116110921078788755686672
9511.44.51.930±0.828±0.81494145613821367925887813797
12012.94.51.931±0.829±0.817591719164116251039999921905
15014.24.51.933±1.330±0.820411999191819001160111810361018
18516.04.52.035±1.333±0.824352389230222831327128011931174
24018.34.52.137±1.335±1.330262978288328631571152214271407
30020.54.52.240±1.338±1.336413588348634641818176416631641
40023.34.52.343±1.341±1.345124450434043162201213820262001
50026.34.52.447±1.345±1.356235553543254052620254924282401
63030.04.52.550±1.348±1.370396960682867983148306929372907
80033.84.52.654±1.352±1.387658681853885053789370435603527
24017.64.52.137±1.335±1.32996294828562836



30019.64.52.239±1.337±1.33610355734583437




12/20kV 1 Core XLPE insulated PVC Sheathed Power Cable
Nominal cross sectional areasDiameter of conductorInsulation thicknessOuter Sheath ThicknessApprox, overall DiameterCable approx. weight
mmkg/km
YJV YJLVYJVYJLV
mm²±0.1mmmmmmZA/ZBZC/Non-flame retardantZAZBZCNon-flame retardantZAZBZCNon-flame retardant
356.95.51.827±0.825±0.8916888817803711683612598
508.25.51.828±0.827±0.810691039965950790760685671
709.75.51.930±0.828±0.81296126211841168891856778762
9511.45.51.932±1.330±0.815891552146914531020983900883
12012.95.52.034±1.332±0.818721833174417261153111410251007
15014.25.52.035±1.333±0.821582117202520061279123711441125
18516.05.52.137±1.335±0.825592517241823981451140913101290
24018.35.52.239±1.338±1.331593112300529831704165715501528
30020.55.52.242±1.340±1.337643714360135771940189017771754
40023.35.52.345±1.343±1.346434585446244372334227621512125
50026.35.52.448±1.346±1.357645700556555372762269725622534
63030.05.52.552±1.350±1.371927119697269413301322930823051
80033.85.52.757±1.355±1.389548876871486803979390037373703
24017.65.52.239±1.337±1.33126308029752954



30019.65.52.241±1.339±1.33730368135703548




18/20kV.18/30kV 1 Core XLPE insulated PVC Sheathed Power Cable
Nominal cross sectional areasDiameter of conductorInsulation thicknessOuter Sheath ThicknessApprox, overall DiameterCable approx. weight
mmkg/km
YJV YJLVYJVYJLV
mm²±0.1mmmmmmZA/ZBZC/Non-flame retardantZAZBZCNon-flame retardantZAZBZCNon-flame retardant
508.28.02.034±1.332±1.3132812881199118110501010920902
709.78.02.035±1.333±1.315621521142814091158111610221004
9511.48.02.137±1.335±1.318841841174217221316127311741153
12012.98.02.139±1.337±1.321652121201719961447140212981277
15014.28.02.240±1.338±1.324792431232222991601155314431421
18516.08.02.342±1.340±1.328962842272727031789173516191595
24018.38.02.344±1.342±1.334973440331832922042198518631837
30020.58.02.447±1.345±1.341394076394639192315225321232096
40023.38.02.550±1.348±1.350424973483448042740267025282499
50026.38.02.654±1.352±1.361956123597159393194312229692937
63030.08.02.758±1.356±1.376547574740973743763368335193484
80033.88.02.862±1.360±1.394249336915891204450436141824144
24017.68.02.344±1.342±1.33458340232823257



30019.68.02.446±1.344±1.34097403639093882




21/35kV 1 Core XLPE insulated PVC Sheathed Power Cable
Nominal cross sectional areasDiameter of conductorInsulation thicknessOuter Sheath ThicknessApprox, overall DiameterCable approx. weight
mmkg/km
YJV YJLVYJVYJLV
mm²±0.1mmmmmmZA/ZBZC/Non-flame retardantZAZBZCNon-flame retardantZAZBZCNon-flame retardant
508.29.32.139±1.337±1.315791579147114491301130111931171
709.79.32.240±1.339±1.318451845173217091441144113271304
9511.49.32.242±1.341±1.321542154203620121586158614681444
12012.99.32.344±1.342±1.324582458233323081739173916 151589
15014.29.32.345±1.344±1.328382838270926831961196118321805
18516.09.32.447±1.346±1.332613261312630972154215420181990
24018.39.32.549±1.348±1.338873887374437142433243322892259
30020.59.32.552±1.350±1.345134513436343312690269025402508
40023.39.32.655±1.353±1.354245424526352303124312429612926
50026.39.32.758±1.357±1.366716671649864613671367134973460
63030.09.32.863±1.561±1.381398139795279134248424840624022
80033.89.33.067±1.565±1.599489948974697024974497447714728
24017.69.32.549±1.347±1.33847384737063676



30019.69.32.551±1.349±1.34470447043234292




26/35kV 1 Core XLPE insulated PVC Sheathed Power Cable
Nominal cross sectional areasDiameter of conductorInsulation thicknessOuter Sheath ThicknessApprox, overall DiameterCable approx. weight
mmkg/km
YJV YJLVYJVYJLV
mm²±0.1mmmmmmZA/ZBZC/Non-flame retardantZAZBZCNon-flame retardantZAZBZCNon-flame retardant
508.210.52.241±1.339±1.317181718160415801441144113261302
709.710.52.242±1.341±1.319731973185318291569156914491424
9511.410.52.344±1.343±1.323072307218121551739173916131587
12012.910.52.346±1.344±1.325952595246524381878187817471720
15014.210.52.447±1.346±1.330013001286528372125212519881960
18516.010.52.549±1.348±1.334313431328832582325232521812151
24018.310.52.552±1.350±1.340444044389438632590259024402408
30020.510.52.654±1.353±1.347014701454345092878287827192686
40023.310.52.757±1.356±1.356235623545454183325332531543118
50026.310.52.861±1.359±1.368846884670266643884388437023663
63030.010.52.965±1.564±1.583668366817181294475447542804238
80033.810.53.069±1.568±1.51016010160995199065186518649774932
24017.610.52.551±1.349±1.34002400238543823



30019.610.52.653±1.352±1.34655465545004467




Part Ⅴ: Main Technical Data of Cable

Max. D.C Resistance of Conductor at 20℃

Nominal cross sectional areas of conductor
mm2

Copper Conductor

Aluminum Conductor

Max. D.C resistance of conductor at 20℃

Max. A.C resistance of conductor at 20℃

Max. D.C resistance of conductor at 20℃

Max. A.C resistance of conductor at 20℃

25

0.727

0.9271

1.200

1.5386

35

0.524

0.6683

0.868

1.1130

50

0.387

0.4937

0.641

0.8220

70

0.268

0.3421

0.443

0.5682

95

0.193

0.2466

0.320

0.4106

120

0.153

0.1958

0.253

0.3248

150

0.124

0.1590

0.206

0.2647

185

0.0991

0.1275

0.164

0.2110

240

0.0754

0.0977

0.125

0.1612

300

0.0601

0.0787

0.100

0.1295

400

0.0470

0.0627

0.0778

0.1015

500

0.0366

0.0503

0.0605

0.0813

630

0.0283

0.0371

0.0469

0.0604

800

0.0221

0.0295

0.0367

0.0475

1000

0.0176

0.0242

-

-

1200

0.0151

0.0213

-

-

1400

0.0129

0.0188

-

-

1600

0.0113

0.0170

-

-


Voltage Test and Partial Discharge

No.Test ItemsRated Voltage (kV)
3.6/6June 68.7/10December 2018/2021/3526/35
June 108.7/1518/30
1Power frequency A.C. voltage test12.52130.5426373.591
kV/5min
2High-voltage test for 4 hours14.42435487284104
kV
3Partial discharge test Maximum discharge at 1. 73 Uo5555555
pC


No.Test ItemRated Voltage (kV)
3.6/6June 68.7/10December 2018/2021/3526/35
June 108.7/1518/30
1Impulse voltage test607595125170200200
kV


Part Ⅵ: Products Details

1. Conductor: 99.99% purity oxygen-free copper, small resistance, more stable for long time use under full load.


2


The aluminum conductor is made of high quality oxygen-free copper, which has high conductivity and oxidation resistance.


3

2. XLPE Insulation: Silicone cross-linked material can withstand temperatures up to 90 degrees Celsius.


4


3. Low eccentricity: The cable is produced by automatic equipment and meets all testing indexes. The thickness of the sheath is uniform to prevent the current from breaking through the sheath and causing a fire.


5


4. Internally filled with anti-pull rope: Effectively prevent the cable from loosening and improve the service life of the wire.


6


5. Armor protection layer: increase the mechanical strength of the cable and improve the ability to release erosion.


7


Part Ⅶ: Application

8


Part Ⅷ: Packaging and Transportation

9

Packing Material:

Steel Wooden Drum (Fumigation)

Cable length in each drum: 500m/1000m or as per actual cable length requirements.


10


Delivery:

Port: Shanghai, or other ports as per your requirements.


Part Ⅸ: Factory Tour

11


Part Ⅹ: Service Guarantee

● Quickly and professional response;

● Excellent quality with reasonable price;

● Sufficient support for our tendering representatives;

● OEM service available based on official & legal authorization;

● Strict quality control system;

● Faster lead time than our competitors;

● Cable solutions to your particular requirements;

● Free sample is available with economic express fee;

● 12 months quality guarantee after delivery.


Part Ⅺ: FAQ

Q1: When can I get the price?

We usually quote within 6 hours after we get your inquiry. If you are very urgent to get the price, please call us or tell us in your email so that we will regard your inquiry priority.


Q2: How can I get a sample to check your quality?

After price confirmation, you can require for samples to check our quality. Sample is free, but the freight charge should be paid.


Q3: How long can I expect to get the sample?

After you pay the freight charge and send us confirmed files, the samples will be ready for delivery in 3-7 days.

The samples will be sent to you via express and arrive in 3~5 days.