MV XLPE insulated power cable, either chemical method or physical method had been employed to transform the molecular structure of PE from chain into three-dimensional network, i.e. thermoplastic PE had been transformed into thermosetting XLPE. After cross-linking, the heat-mechanical properties of the cable have been greatly improved while its excellent electrical are still maintained.
The nominal conductor operating temperature of XLPE insulated power cable is 90°C which is higher than that of paper, PVC or PE insulated power cable. The cable has the advantages of simplicity in construction, lightness in weight, besides its excellent electrical, heat-mechanical and anti-chemical corrosion properties. It can also be laid with no limitation of level difference along the route.
Part Ⅰ: Operating Characteristics
1. Type: YJV (Copper Conductor XLPE insulated PVC sheathed power cable)
YJLV (Aluminum Conductor XLPE insulated PVC sheathed power cable)
YJY (Copper Conductor XLPE insulated PE sheathed power cable)
YJLV (Aluminum Conductor XLPE insulated PE sheathed power cable)
YJV62 (Copper conductor XLPE insulated non-magnetic metal tape armoured PVC sheathed Power cable)
YJLV62 (Aluminium conductor XLPE insulated non-magnetic metal tape armoured PVC sheathed Power cable)
YJV63 (Copper conductor XLPE insulated non-magnetic metal tape armoured PE sheathed Power cable)
YJLV63 (Aluminium conductor XLPE insulated non-magnetic metal tape armoured PEsheathed Power cable)
YJV22 (Copper Conductor XLPE insulated steel tape armored PVC sheathed power cable)
YJLV22 (Aluminum Conductor XLPE insulated steel tape armored PVC sheathed power cable)
YJV23 (Copper conductor XLPE insulated steel tape armoured PE sheathed power cable)
YJLV23 (Aluminium conductor XLPE insulated steel tape armoured PE sheathed power cable)
YJL72 (Copper conductor XLPE insulated non-magnetic metal wire armoured PVC sheathed power cable)
YJLV72 (Aluminum conductor XLPE insulated non-magnetic metal wire armoured PVC sheathed power cable)
YJV73 (Copper conductor XLPE insulated non-magnetic metal wire armoured PE sheathed power cable)
YJLV73 (Aluminum conductor XLPE insulated non-magnetic metal wire armoured PE sheathed power cable)
YJV32 (Copper Conductor XLPE insulated fine steel wire armored PVC sheathed power cable)
YJLV32 (Aluminum Conductor XLPE insulated fine steel wire armored PVC sheathed power cable)
YJV33 (Copper conductor XLPE insulated fine steel wire armoured PE sheathed power cable)
YJLV33 (Aluminium conductor XLPE insulated fine steel wire armoured PE sheathed power cable)
YJV42 (Copper core XLPE insulated thick steel wire armoured PVC sheathed power cable)
YJLV42 (Aluminum core XLPE insulated thick steel wire armoured PVC sheathed power cable)
YJV43 (Copper core XLPE insulated steel thick wire armoured PE sheathed power cable)
YJLV43 (Aluminium core XLPE insulated thick steel wire armoured PE sheathed power cable)
2. Rated power-frequency voltage Uo/U: 3.6/6kV ~26/35kV
3. Conductor: Oxygen-free Copper/Oxygen-free Aluminum
4. Insulation: XLPE
5. Sheathing: PVC/PE
6. Armored: Steel tape Armored (YJV22, YJLV22, YJV23, YJLV23)
Fine steel wire Armored (YJV32, YJLV32, YJV33, YJLV33)
Non-magnetic metal tape armored (YJV62,YJLV62, YJV63, YJLV63)
Non-magnetic metal wire armored (YJV72, YJLV72, YJV73, YJLV73)
Thick steel wire armored (YLV42, YJLV42, YJV43, YJLV43)
7. Max. admissible operating temperature of conductor: 90℃ (XLPE insulation)
8. Max. Short-circurt temperature of conductor shall not exceeding 250℃ (Max. sustaining period not exceeding 5S)
9. The installation temperature should be not below 0℃.
10. The bending radius of three-cores unarmored cable should not less than 15 times, and the bending radius of three-cores armored cable should not less than 12 times.
The bending radius of single core unarmored cable should not less than 20 times and the bending radius of single core armored cable should not less than 15 times.
Part Ⅱ: Range of Production
Structure | Cores | Rated Voltage (kV) | 3.6/6 | 6/6 | 8.7/10 | 12/15 | 18/20 | 21/35 | 26/35 |
Unarmored | 1 | Type | YJV YJLV YJY YJLY | YJSV YJLSV | |||||
Nominal cross sectional of areas (mm2) | 25~630 | 25~800 | 25~800 | 35~800 | 50~800 | 50~800 | 50~800 | ||
3 | Type | YJV YJLV YJY YJLY | |||||||
Nominal cross sectional of areas (mm2) | 25~630 | 25~630 | 25~630 | 35~630 | 50~500 | 50~500 | 50~500 | ||
Non-magnetic | 1 | Type | YJV62 YJLV62 YJV63 YJLV63 | YJSV62 YJLSV62 | |||||
Nominal cross sectional of areas (mm2) | 25~630 | 25~800 | 25~800 | 35~800 | 50~800 | 50~800 | 50~800 | ||
Steel tape armored | 3 | Type | YJV22 YJLV22 YJV23 YJLV23 | ||||||
Nominal cross sectional of areas (mm2) | 25~630 | 25~630 | 25~630 | 35~630 | 50~500 | 50~500 | 50~500 | ||
Non-magnetic metal wire armored | 1 | Type | YJV72 YJLV72 YJV73 YJLV73 | YJSV72 YJLSV72 | |||||
Nominal cross sectional of areas (mm2) | 25~630 | 25~800 | 25~800 | 35~800 | 50~800 | 50~800 | 50~800 | ||
Steel wire | 3 | Type | YJV32 YJLV32 YJV33 YJLV33 | ||||||
Nominal cross sectional of areas (mm2) | 25~630 | 25~630 | 25~500 | 35~500 | 50~400 | 50~300 | 50~185 | ||
Thick Steel | 1/3 | Type | YJV42 YJLV42 YJV43 YJLV43 | ||||||
Nominal cross sectional of areas (mm2) | 25~630 | 25~630 | 25~500 | 35~500 | 50~400 | 50~300 | 50~185 | ||
Part Ⅲ: Construction

The type conductor is compact and the circular conductor is made up of round conductor wires. The comparison diagrams of the two conductor structures are shown above. Both meet the national standard.
Compared with circular conductor, type conductor:
1) More compact and higher compression coefficient;
2) Better waterproof performance;
3) The field intensity distribution on the conductor's surface is more uniform;
4) Can avoid the conductor shield stuck between the conductor stranded;
5) For the same specification, the diameter of the type conductor is smaller, so that the cable is more affordable.
Part Ⅳ: Construction and Main Technical Data
| 3.6/6kV 1 Core XLPE insulated PVC Sheathed Power Cable | |||||||||||||
| Nominal cross sectional areas | Diameter of conductor | Insulation thickness | Outer Sheath Thickness | Approx, overall Diameter | Cable approx. weight | ||||||||
| mm | kg/km | ||||||||||||
| YJV YJLV | YJV | YJLV | |||||||||||
| mm² | ±0.1mm | mm | mm | ZA/ZB | ZC/Non-flame retardant | ZA | ZB | ZC | Non-flame retardant | ZA | ZB | ZC | Non-flame retardant |
| 25 | 5.9 | 2.5 | 1.8 | 21±0.8 | 19±0.8 | 580 | 556 | 506 | 496 | 432 | 408 | 358 | 348 |
| 35 | 6.9 | 2.5 | 1.8 | 22±0.8 | 20±0.8 | 691 | 665 | 613 | 603 | 485 | 459 | 407 | 396 |
| 50 | 8.2 | 2.5 | 1.8 | 23±0.8 | 21±0.8 | 833 | 806 | 750 | 739 | 553 | 526 | 470 | 459 |
| 70 | 9.7 | 2.5 | 1.8 | 24±0.8 | 22±0.8 | 1038 | 1010 | 951 | 939 | 632 | 603 | 544 | 532 |
| 95 | 11.4 | 2.5 | 1.8 | 26±0.8 | 24±0.8 | 1316 | 1286 | 1222 | 1209 | 746 | 716 | 652 | 639 |
| 120 | 12.9 | 2.5 | 1.8 | 27±0.8 | 25±0.8 | 1572 | 1540 | 1473 | 1459 | 852 | 820 | 752 | 738 |
| 150 | 14.2 | 2.5 | 1.8 | 29±0.8 | 27±0.8 | 1847 | 1813 | 1742 | 1727 | 964 | 930 | 858 | 843 |
| 185 | 16.0 | 2.5 | 1.9 | 31±0.8 | 29±0.8 | 2229 | 2189 | 2113 | 2097 | 1120 | 1081 | 1004 | 988 |
| 240 | 18.3 | 2.6 | 1.9 | 34±1.3 | 31±0.8 | 2801 | 2758 | 2675 | 2657 | 1345 | 1302 | 1219 | 1201 |
| 300 | 20.5 | 2.8 | 2.0 | 36±1.3 | 34±1.3 | 3423 | 3375 | 3284 | 3264 | 1600 | 1552 | 1461 | 1441 |
| 400 | 23.3 | 3.0 | 2.2 | 40±1.3 | 38±1.3 | 4320 | 4266 | 4164 | 4142 | 2006 | 1951 | 1847 | 1824 |
| 500 | 26.3 | 3.2 | 2.3 | 44±1.3 | 42±1.3 | 5442 | 5377 | 5264 | 5239 | 2438 | 2373 | 2259 | 2234 |
| 630 | 30.0 | 3.2 | 2.4 | 48±1.3 | 46±1.3 | 6843 | 6770 | 6645 | 6618 | 2952 | 2879 | 2755 | 2727 |
| 240 | 17.6 | 2.6 | 1.9 | 33±1.3 | 30±0.8 | 2774 | 2733 | 2651 | 2634 | ||||
| 300 | 19.6 | 2.8 | 2.0 | 35±1.3 | 34±1.3 | 3397 | 3350 | 3261 | 3242 | ||||
| 6/6kV.6/10kV 1 Core XLPE insulated PVC Sheathed Power Cable | |||||||||||||
| Nominal cross sectional areas | Diameter of conductor | Insulation thickness | Outer Sheath Thickness | Approx, overall Diameter | Cable approx. weight | ||||||||
| mm | kg/km | ||||||||||||
| YJV YJLV | YJV | YJLV | |||||||||||
| mm² | ±0.1mm | mm | mm | ZA/ZB | ZC/Non-flame retardant | ZA | ZB | ZC | Non-flame retardant | ZA | ZB | ZC | Non-flame retardant |
| 25 | 5.9 | 3.4 | 1.8 | 22±0.8 | 20±0.8 | 639 | 613 | 559 | 548 | 491 | 465 | 411 | 400 |
| 35 | 6.9 | 3.4 | 1.8 | 23±0.8 | 21±0.8 | 752 | 725 | 668 | 657 | 547 | 519 | 462 | 451 |
| 50 | 8.2 | 3.4 | 1.8 | 25±0.8 | 23±0.8 | 898 | 869 | 809 | 796 | 618 | 589 | 529 | 516 |
| 70 | 9.7 | 3.4 | 1.8 | 26±0.8 | 24±0.8 | 1105 | 1075 | 1012 | 999 | 699 | 669 | 605 | 592 |
| 95 | 11.4 | 3.4 | 1.8 | 27±0.8 | 25±0.8 | 1387 | 1355 | 1287 | 1273 | 818 | 785 | 717 | 703 |
| 120 | 12.9 | 3.4 | 1.8 | 29±0.8 | 27±0.8 | 1647 | 1613 | 1541 | 1526 | 927 | 893 | 821 | 806 |
| 150 | 14.2 | 3.4 | 1.9 | 30±0.8 | 28±0.8 | 1938 | 1899 | 1823 | 1807 | 1057 | 1017 | 940 | 924 |
| 185 | 16.0 | 3.4 | 1.9 | 33±1.3 | 30±0.8 | 2312 | 2270 | 2189 | 2172 | 1203 | 1161 | 1080 | 1063 |
| 240 | 18.3 | 3.4 | 2.0 | 35±1.3 | 33±1.3 | 2894 | 2848 | 2760 | 2741 | 1438 | 1392 | 1304 | 1285 |
| 300 | 20.5 | 3.4 | 2.1 | 38±1.3 | 36±1.3 | 3501 | 3452 | 3357 | 3337 | 1677 | 1629 | 1534 | 1513 |
| 400 | 23.3 | 3.4 | 2.2 | 41±1.3 | 39±1.3 | 4361 | 4306 | 4202 | 4180 | 2048 | 1992 | 1886 | 1863 |
| 500 | 26.3 | 3.4 | 2.3 | 44±1.3 | 42±1.3 | 5459 | 5394 | 5280 | 5255 | 2455 | 2390 | 2275 | 2250 |
| 630 | 30.0 | 3.4 | 2.4 | 48±1.3 | 46±1.3 | 6861 | 6788 | 6663 | 6635 | 2970 | 2897 | 2772 | 2744 |
| 800 | 33.8 | 3.4 | 2.5 | 52±1.3 | 50±1.3 | 8574 | 8491 | 8354 | 8324 | 3596 | 3514 | 3376 | 3345 |
| 240 | 17.6 | 3.4 | 2.0 | 34±1.3 | 33±1.3 | 2866 | 2820 | 2734 | 2716 | ||||
| 300 | 19.6 | 3.4 | 2.1 | 37±1.3 | 35±1.3 | 3472 | 3425 | 3332 | 3312 | ||||
| 8.7/10kV.8.7/15kV 1 Core XLPE insulated PVC Sheathed Power Cable | |||||||||||||
| Nominal cross sectional areas | Diameter of conductor | Insulation thickness | Outer Sheath Thickness | Approx, overall Diameter | Cable approx. weight | ||||||||
| mm | kg/km | ||||||||||||
| YJV YJLV | YJV | YJLV | |||||||||||
| mm² | ±0.1mm | mm | mm | ZA/ZB | ZC/Non-flame retardant | ZA | ZB | ZC | Non-flame retardant | ZA | ZB | ZC | Non-flame retardant |
| 25 | 5.9 | 4.5 | 1.8 | 24±0.8 | 22±0.8 | 718 | 689 | 630 | 618 | 570 | 542 | 482 | 470 |
| 35 | 6.9 | 4.5 | 1.8 | 25±0.8 | 23±0.8 | 834 | 804 | 742 | 729 | 628 | 599 | 536 | 524 |
| 50 | 8.2 | 4.5 | 1.8 | 27±0.8 | 25±0.8 | 983 | 952 | 886 | 873 | 704 | 672 | 607 | 593 |
| 70 | 9.7 | 4.5 | 1.8 | 28±0.8 | 26±0.8 | 1194 | 1161 | 1092 | 1078 | 788 | 755 | 686 | 672 |
| 95 | 11.4 | 4.5 | 1.9 | 30±0.8 | 28±0.8 | 1494 | 1456 | 1382 | 1367 | 925 | 887 | 813 | 797 |
| 120 | 12.9 | 4.5 | 1.9 | 31±0.8 | 29±0.8 | 1759 | 1719 | 1641 | 1625 | 1039 | 999 | 921 | 905 |
| 150 | 14.2 | 4.5 | 1.9 | 33±1.3 | 30±0.8 | 2041 | 1999 | 1918 | 1900 | 1160 | 1118 | 1036 | 1018 |
| 185 | 16.0 | 4.5 | 2.0 | 35±1.3 | 33±0.8 | 2435 | 2389 | 2302 | 2283 | 1327 | 1280 | 1193 | 1174 |
| 240 | 18.3 | 4.5 | 2.1 | 37±1.3 | 35±1.3 | 3026 | 2978 | 2883 | 2863 | 1571 | 1522 | 1427 | 1407 |
| 300 | 20.5 | 4.5 | 2.2 | 40±1.3 | 38±1.3 | 3641 | 3588 | 3486 | 3464 | 1818 | 1764 | 1663 | 1641 |
| 400 | 23.3 | 4.5 | 2.3 | 43±1.3 | 41±1.3 | 4512 | 4450 | 4340 | 4316 | 2201 | 2138 | 2026 | 2001 |
| 500 | 26.3 | 4.5 | 2.4 | 47±1.3 | 45±1.3 | 5623 | 5553 | 5432 | 5405 | 2620 | 2549 | 2428 | 2401 |
| 630 | 30.0 | 4.5 | 2.5 | 50±1.3 | 48±1.3 | 7039 | 6960 | 6828 | 6798 | 3148 | 3069 | 2937 | 2907 |
| 800 | 33.8 | 4.5 | 2.6 | 54±1.3 | 52±1.3 | 8765 | 8681 | 8538 | 8505 | 3789 | 3704 | 3560 | 3527 |
| 240 | 17.6 | 4.5 | 2.1 | 37±1.3 | 35±1.3 | 2996 | 2948 | 2856 | 2836 | ||||
| 300 | 19.6 | 4.5 | 2.2 | 39±1.3 | 37±1.3 | 3610 | 3557 | 3458 | 3437 | ||||
| 12/20kV 1 Core XLPE insulated PVC Sheathed Power Cable | |||||||||||||
| Nominal cross sectional areas | Diameter of conductor | Insulation thickness | Outer Sheath Thickness | Approx, overall Diameter | Cable approx. weight | ||||||||
| mm | kg/km | ||||||||||||
| YJV YJLV | YJV | YJLV | |||||||||||
| mm² | ±0.1mm | mm | mm | ZA/ZB | ZC/Non-flame retardant | ZA | ZB | ZC | Non-flame retardant | ZA | ZB | ZC | Non-flame retardant |
| 35 | 6.9 | 5.5 | 1.8 | 27±0.8 | 25±0.8 | 916 | 888 | 817 | 803 | 711 | 683 | 612 | 598 |
| 50 | 8.2 | 5.5 | 1.8 | 28±0.8 | 27±0.8 | 1069 | 1039 | 965 | 950 | 790 | 760 | 685 | 671 |
| 70 | 9.7 | 5.5 | 1.9 | 30±0.8 | 28±0.8 | 1296 | 1262 | 1184 | 1168 | 891 | 856 | 778 | 762 |
| 95 | 11.4 | 5.5 | 1.9 | 32±1.3 | 30±0.8 | 1589 | 1552 | 1469 | 1453 | 1020 | 983 | 900 | 883 |
| 120 | 12.9 | 5.5 | 2.0 | 34±1.3 | 32±0.8 | 1872 | 1833 | 1744 | 1726 | 1153 | 1114 | 1025 | 1007 |
| 150 | 14.2 | 5.5 | 2.0 | 35±1.3 | 33±0.8 | 2158 | 2117 | 2025 | 2006 | 1279 | 1237 | 1144 | 1125 |
| 185 | 16.0 | 5.5 | 2.1 | 37±1.3 | 35±0.8 | 2559 | 2517 | 2418 | 2398 | 1451 | 1409 | 1310 | 1290 |
| 240 | 18.3 | 5.5 | 2.2 | 39±1.3 | 38±1.3 | 3159 | 3112 | 3005 | 2983 | 1704 | 1657 | 1550 | 1528 |
| 300 | 20.5 | 5.5 | 2.2 | 42±1.3 | 40±1.3 | 3764 | 3714 | 3601 | 3577 | 1940 | 1890 | 1777 | 1754 |
| 400 | 23.3 | 5.5 | 2.3 | 45±1.3 | 43±1.3 | 4643 | 4585 | 4462 | 4437 | 2334 | 2276 | 2151 | 2125 |
| 500 | 26.3 | 5.5 | 2.4 | 48±1.3 | 46±1.3 | 5764 | 5700 | 5565 | 5537 | 2762 | 2697 | 2562 | 2534 |
| 630 | 30.0 | 5.5 | 2.5 | 52±1.3 | 50±1.3 | 7192 | 7119 | 6972 | 6941 | 3301 | 3229 | 3082 | 3051 |
| 800 | 33.8 | 5.5 | 2.7 | 57±1.3 | 55±1.3 | 8954 | 8876 | 8714 | 8680 | 3979 | 3900 | 3737 | 3703 |
| 240 | 17.6 | 5.5 | 2.2 | 39±1.3 | 37±1.3 | 3126 | 3080 | 2975 | 2954 | ||||
| 300 | 19.6 | 5.5 | 2.2 | 41±1.3 | 39±1.3 | 3730 | 3681 | 3570 | 3548 | ||||
| 18/20kV.18/30kV 1 Core XLPE insulated PVC Sheathed Power Cable | |||||||||||||
| Nominal cross sectional areas | Diameter of conductor | Insulation thickness | Outer Sheath Thickness | Approx, overall Diameter | Cable approx. weight | ||||||||
| mm | kg/km | ||||||||||||
| YJV YJLV | YJV | YJLV | |||||||||||
| mm² | ±0.1mm | mm | mm | ZA/ZB | ZC/Non-flame retardant | ZA | ZB | ZC | Non-flame retardant | ZA | ZB | ZC | Non-flame retardant |
| 50 | 8.2 | 8.0 | 2.0 | 34±1.3 | 32±1.3 | 1328 | 1288 | 1199 | 1181 | 1050 | 1010 | 920 | 902 |
| 70 | 9.7 | 8.0 | 2.0 | 35±1.3 | 33±1.3 | 1562 | 1521 | 1428 | 1409 | 1158 | 1116 | 1022 | 1004 |
| 95 | 11.4 | 8.0 | 2.1 | 37±1.3 | 35±1.3 | 1884 | 1841 | 1742 | 1722 | 1316 | 1273 | 1174 | 1153 |
| 120 | 12.9 | 8.0 | 2.1 | 39±1.3 | 37±1.3 | 2165 | 2121 | 2017 | 1996 | 1447 | 1402 | 1298 | 1277 |
| 150 | 14.2 | 8.0 | 2.2 | 40±1.3 | 38±1.3 | 2479 | 2431 | 2322 | 2299 | 1601 | 1553 | 1443 | 1421 |
| 185 | 16.0 | 8.0 | 2.3 | 42±1.3 | 40±1.3 | 2896 | 2842 | 2727 | 2703 | 1789 | 1735 | 1619 | 1595 |
| 240 | 18.3 | 8.0 | 2.3 | 44±1.3 | 42±1.3 | 3497 | 3440 | 3318 | 3292 | 2042 | 1985 | 1863 | 1837 |
| 300 | 20.5 | 8.0 | 2.4 | 47±1.3 | 45±1.3 | 4139 | 4076 | 3946 | 3919 | 2315 | 2253 | 2123 | 2096 |
| 400 | 23.3 | 8.0 | 2.5 | 50±1.3 | 48±1.3 | 5042 | 4973 | 4834 | 4804 | 2740 | 2670 | 2528 | 2499 |
| 500 | 26.3 | 8.0 | 2.6 | 54±1.3 | 52±1.3 | 6195 | 6123 | 5971 | 5939 | 3194 | 3122 | 2969 | 2937 |
| 630 | 30.0 | 8.0 | 2.7 | 58±1.3 | 56±1.3 | 7654 | 7574 | 7409 | 7374 | 3763 | 3683 | 3519 | 3484 |
| 800 | 33.8 | 8.0 | 2.8 | 62±1.3 | 60±1.3 | 9424 | 9336 | 9158 | 9120 | 4450 | 4361 | 4182 | 4144 |
| 240 | 17.6 | 8.0 | 2.3 | 44±1.3 | 42±1.3 | 3458 | 3402 | 3282 | 3257 | ||||
| 300 | 19.6 | 8.0 | 2.4 | 46±1.3 | 44±1.3 | 4097 | 4036 | 3909 | 3882 | ||||
| 21/35kV 1 Core XLPE insulated PVC Sheathed Power Cable | |||||||||||||
| Nominal cross sectional areas | Diameter of conductor | Insulation thickness | Outer Sheath Thickness | Approx, overall Diameter | Cable approx. weight | ||||||||
| mm | kg/km | ||||||||||||
| YJV YJLV | YJV | YJLV | |||||||||||
| mm² | ±0.1mm | mm | mm | ZA/ZB | ZC/Non-flame retardant | ZA | ZB | ZC | Non-flame retardant | ZA | ZB | ZC | Non-flame retardant |
| 50 | 8.2 | 9.3 | 2.1 | 39±1.3 | 37±1.3 | 1579 | 1579 | 1471 | 1449 | 1301 | 1301 | 1193 | 1171 |
| 70 | 9.7 | 9.3 | 2.2 | 40±1.3 | 39±1.3 | 1845 | 1845 | 1732 | 1709 | 1441 | 1441 | 1327 | 1304 |
| 95 | 11.4 | 9.3 | 2.2 | 42±1.3 | 41±1.3 | 2154 | 2154 | 2036 | 2012 | 1586 | 1586 | 1468 | 1444 |
| 120 | 12.9 | 9.3 | 2.3 | 44±1.3 | 42±1.3 | 2458 | 2458 | 2333 | 2308 | 1739 | 1739 | 16 15 | 1589 |
| 150 | 14.2 | 9.3 | 2.3 | 45±1.3 | 44±1.3 | 2838 | 2838 | 2709 | 2683 | 1961 | 1961 | 1832 | 1805 |
| 185 | 16.0 | 9.3 | 2.4 | 47±1.3 | 46±1.3 | 3261 | 3261 | 3126 | 3097 | 2154 | 2154 | 2018 | 1990 |
| 240 | 18.3 | 9.3 | 2.5 | 49±1.3 | 48±1.3 | 3887 | 3887 | 3744 | 3714 | 2433 | 2433 | 2289 | 2259 |
| 300 | 20.5 | 9.3 | 2.5 | 52±1.3 | 50±1.3 | 4513 | 4513 | 4363 | 4331 | 2690 | 2690 | 2540 | 2508 |
| 400 | 23.3 | 9.3 | 2.6 | 55±1.3 | 53±1.3 | 5424 | 5424 | 5263 | 5230 | 3124 | 3124 | 2961 | 2926 |
| 500 | 26.3 | 9.3 | 2.7 | 58±1.3 | 57±1.3 | 6671 | 6671 | 6498 | 6461 | 3671 | 3671 | 3497 | 3460 |
| 630 | 30.0 | 9.3 | 2.8 | 63±1.5 | 61±1.3 | 8139 | 8139 | 7952 | 7913 | 4248 | 4248 | 4062 | 4022 |
| 800 | 33.8 | 9.3 | 3.0 | 67±1.5 | 65±1.5 | 9948 | 9948 | 9746 | 9702 | 4974 | 4974 | 4771 | 4728 |
| 240 | 17.6 | 9.3 | 2.5 | 49±1.3 | 47±1.3 | 3847 | 3847 | 3706 | 3676 | ||||
| 300 | 19.6 | 9.3 | 2.5 | 51±1.3 | 49±1.3 | 4470 | 4470 | 4323 | 4292 | ||||
| 26/35kV 1 Core XLPE insulated PVC Sheathed Power Cable | |||||||||||||
| Nominal cross sectional areas | Diameter of conductor | Insulation thickness | Outer Sheath Thickness | Approx, overall Diameter | Cable approx. weight | ||||||||
| mm | kg/km | ||||||||||||
| YJV YJLV | YJV | YJLV | |||||||||||
| mm² | ±0.1mm | mm | mm | ZA/ZB | ZC/Non-flame retardant | ZA | ZB | ZC | Non-flame retardant | ZA | ZB | ZC | Non-flame retardant |
| 50 | 8.2 | 10.5 | 2.2 | 41±1.3 | 39±1.3 | 1718 | 1718 | 1604 | 1580 | 1441 | 1441 | 1326 | 1302 |
| 70 | 9.7 | 10.5 | 2.2 | 42±1.3 | 41±1.3 | 1973 | 1973 | 1853 | 1829 | 1569 | 1569 | 1449 | 1424 |
| 95 | 11.4 | 10.5 | 2.3 | 44±1.3 | 43±1.3 | 2307 | 2307 | 2181 | 2155 | 1739 | 1739 | 1613 | 1587 |
| 120 | 12.9 | 10.5 | 2.3 | 46±1.3 | 44±1.3 | 2595 | 2595 | 2465 | 2438 | 1878 | 1878 | 1747 | 1720 |
| 150 | 14.2 | 10.5 | 2.4 | 47±1.3 | 46±1.3 | 3001 | 3001 | 2865 | 2837 | 2125 | 2125 | 1988 | 1960 |
| 185 | 16.0 | 10.5 | 2.5 | 49±1.3 | 48±1.3 | 3431 | 3431 | 3288 | 3258 | 2325 | 2325 | 2181 | 2151 |
| 240 | 18.3 | 10.5 | 2.5 | 52±1.3 | 50±1.3 | 4044 | 4044 | 3894 | 3863 | 2590 | 2590 | 2440 | 2408 |
| 300 | 20.5 | 10.5 | 2.6 | 54±1.3 | 53±1.3 | 4701 | 4701 | 4543 | 4509 | 2878 | 2878 | 2719 | 2686 |
| 400 | 23.3 | 10.5 | 2.7 | 57±1.3 | 56±1.3 | 5623 | 5623 | 5454 | 5418 | 3325 | 3325 | 3154 | 3118 |
| 500 | 26.3 | 10.5 | 2.8 | 61±1.3 | 59±1.3 | 6884 | 6884 | 6702 | 6664 | 3884 | 3884 | 3702 | 3663 |
| 630 | 30.0 | 10.5 | 2.9 | 65±1.5 | 64±1.5 | 8366 | 8366 | 8171 | 8129 | 4475 | 4475 | 4280 | 4238 |
| 800 | 33.8 | 10.5 | 3.0 | 69±1.5 | 68±1.5 | 10160 | 10160 | 9951 | 9906 | 5186 | 5186 | 4977 | 4932 |
| 240 | 17.6 | 10.5 | 2.5 | 51±1.3 | 49±1.3 | 4002 | 4002 | 3854 | 3823 | ||||
| 300 | 19.6 | 10.5 | 2.6 | 53±1.3 | 52±1.3 | 4655 | 4655 | 4500 | 4467 | ||||
Part Ⅴ: Main Technical Data of Cable
Max. D.C Resistance of Conductor at 20℃
Nominal cross sectional areas of conductor | Copper Conductor | Aluminum Conductor | ||
Max. D.C resistance of conductor at 20℃ | Max. A.C resistance of conductor at 20℃ | Max. D.C resistance of conductor at 20℃ | Max. A.C resistance of conductor at 20℃ | |
25 | 0.727 | 0.9271 | 1.200 | 1.5386 |
35 | 0.524 | 0.6683 | 0.868 | 1.1130 |
50 | 0.387 | 0.4937 | 0.641 | 0.8220 |
70 | 0.268 | 0.3421 | 0.443 | 0.5682 |
95 | 0.193 | 0.2466 | 0.320 | 0.4106 |
120 | 0.153 | 0.1958 | 0.253 | 0.3248 |
150 | 0.124 | 0.1590 | 0.206 | 0.2647 |
185 | 0.0991 | 0.1275 | 0.164 | 0.2110 |
240 | 0.0754 | 0.0977 | 0.125 | 0.1612 |
300 | 0.0601 | 0.0787 | 0.100 | 0.1295 |
400 | 0.0470 | 0.0627 | 0.0778 | 0.1015 |
500 | 0.0366 | 0.0503 | 0.0605 | 0.0813 |
630 | 0.0283 | 0.0371 | 0.0469 | 0.0604 |
800 | 0.0221 | 0.0295 | 0.0367 | 0.0475 |
1000 | 0.0176 | 0.0242 | - | - |
1200 | 0.0151 | 0.0213 | - | - |
1400 | 0.0129 | 0.0188 | - | - |
1600 | 0.0113 | 0.0170 | - | - |
Voltage Test and Partial Discharge
| No. | Test Items | Rated Voltage (kV) | ||||||
| 3.6/6 | June 6 | 8.7/10 | December 20 | 18/20 | 21/35 | 26/35 | ||
| June 10 | 8.7/15 | 18/30 | ||||||
| 1 | Power frequency A.C. voltage test | 12.5 | 21 | 30.5 | 42 | 63 | 73.5 | 91 |
| kV/5min | ||||||||
| 2 | High-voltage test for 4 hours | 14.4 | 24 | 35 | 48 | 72 | 84 | 104 |
| kV | ||||||||
| 3 | Partial discharge test Maximum discharge at 1. 73 Uo | 5 | 5 | 5 | 5 | 5 | 5 | 5 |
| pC | ||||||||
| No. | Test Item | Rated Voltage (kV) | ||||||
| 3.6/6 | June 6 | 8.7/10 | December 20 | 18/20 | 21/35 | 26/35 | ||
| June 10 | 8.7/15 | 18/30 | ||||||
| 1 | Impulse voltage test | 60 | 75 | 95 | 125 | 170 | 200 | 200 |
| kV | ||||||||
Part Ⅵ: Products Details
1. Conductor: 99.99% purity oxygen-free copper, small resistance, more stable for long time use under full load.

The aluminum conductor is made of high quality oxygen-free copper, which has high conductivity and oxidation resistance.

2. XLPE Insulation: Silicone cross-linked material can withstand temperatures up to 90 degrees Celsius.

3. Low eccentricity: The cable is produced by automatic equipment and meets all testing indexes. The thickness of the sheath is uniform to prevent the current from breaking through the sheath and causing a fire.

4. Internally filled with anti-pull rope: Effectively prevent the cable from loosening and improve the service life of the wire.

5. Armor protection layer: increase the mechanical strength of the cable and improve the ability to release erosion.

Part Ⅶ: Application

Part Ⅷ: Packaging and Transportation

Packing Material:
Steel Wooden Drum (Fumigation)
Cable length in each drum: 500m/1000m or as per actual cable length requirements.

Delivery:
Port: Shanghai, or other ports as per your requirements.
Part Ⅸ: Factory Tour

Part Ⅹ: Service Guarantee
● Quickly and professional response;
● Excellent quality with reasonable price;
● Sufficient support for our tendering representatives;
● OEM service available based on official & legal authorization;
● Strict quality control system;
● Faster lead time than our competitors;
● Cable solutions to your particular requirements;
● Free sample is available with economic express fee;
● 12 months quality guarantee after delivery.
Part Ⅺ: FAQ
Q1: When can I get the price?
We usually quote within 6 hours after we get your inquiry. If you are very urgent to get the price, please call us or tell us in your email so that we will regard your inquiry priority.
Q2: How can I get a sample to check your quality?
After price confirmation, you can require for samples to check our quality. Sample is free, but the freight charge should be paid.
Q3: How long can I expect to get the sample?
After you pay the freight charge and send us confirmed files, the samples will be ready for delivery in 3-7 days.
The samples will be sent to you via express and arrive in 3~5 days.
Q4: What about the lead time for mass production?
Honestly, it depends on the order quantity and the season you place the order. The best record we keep is delivering 10 kilometers cable within a week. Generally speaking, we suggest that you start inquiry two months before the date you would like to get the products at your country.
Hot Tags: mv xlpe insulated power cable 3.6/6kv~26/35kv yjv yjlv cable, China, suppliers, manufacturers, factory, price, made in China